Government Meetings

Agendas, minutes, and meeting recaps for Delaware County municipalities

Recap Available

Marple Township Board of Commissioners — Sep 14, 2026

Monday, September 14, 2026

About this meeting

Marple Township Board of Commissioners in Marple met on Monday, September 14, 2026. County Brief published an AI-labeled recap below, drawn from the official packet. Use the original documents or the official site for the full record, and browse other Marple Township Board of Commissioners meetings from Marple.

Meeting Recap AI-generated summary

Original minutes (PDF) on marpletwp.com ↗Original agenda (PDF) on marpletwp.com ↗

County Brief is an independent local news service from Wisdom Digital Media, Inc. It is not affiliated with, endorsed by, or acting on behalf of any government agency. Meeting agendas and minutes come from each town's or school district's official website; every meeting links to the original document. Official sources

The posting explicitly says that no meeting minutes have been posted for these public notices and that minutes will appear under the designated meeting dates after they are finalized and approved. The available material contains a proposed ordinance to amend Marple Township’s zoning code for data centers and data center accessory uses. It would define data centers and related terms, permit the uses by conditional use in the I Light Industrial District only, and establish development standards. The proposed standards address minimum lot area, building height, setbacks, landscape buffers and fencing, equipment screening, noise and vibration limits, and sound studies. They also require water-supply documentation or feasibility studies, with provisions for groundwater and surface-water impacts, pre-construction well testing, and post-construction monitoring. The text is ordinance language, not a record of deliberation or a vote. It does not show that the Board introduced, adopted, or otherwise acted on the proposal, and no vote or public-hearing outcome is recorded. Accordingly, the posting supports no conclusion that these requirements became law.

Discussed, no vote recorded

  • Proposed zoning standards for data centers and accessory uses
How this recap was made

Written by AI on Nov 21, 2026 from the official minutes linked on this page, then checked by software, not by a reporter. An item is listed under Decided only when the minutes' own wording shows the action, and that wording is quoted. A vote count appears only when the minutes give it. Everything else is listed as discussed. This is not an official record; the linked document is. More on how County Brief works

Report an error

Get Marple meeting agendas and recaps by email

Free. One email when a new agenda or recap for Marple is posted, so you know what is being decided before and after each meeting.

Up to 3 words. You also get the free weekly Delaware County email. Unsubscribe anytime. Privacy

Items in the posted packet

Taken from the official agenda index. This is a list of attachments, not a recap of votes.

  1. The maximum building height for a Data Center shall be 35 feet, plus up to 10 additional feet for roof-mounted equipment such as cooling and ventilation systems, HVAC units, and cooling towers
  2. Data Centers and Data Center Accessory Uses shall be set back a minimum of 1,000 feet from all other adjoining property lines and road rights-of-way
  3. The landscape buffer shall be at least 50 feet in width and may be part of the minimum setback distance
  4. The landscape buffer shall be free of structures, dumpsters, storage or display areas, signs, materials, loading or unloading areas, and vehicle parking
  5. One (1) deciduous canopy (shade) tree per 75 linear feet of buffer, Size of canopy (shade) trees shal! be a minimum of 2% inch caliper at the time of planting
  6. In the event that existing topography and/or vegetation is adequate to meet the intent of the required buffer yard, such existing topography and/or vegetation may constitute all or part of the required buffer yard
  7. Surface water withdrawals. SEE SUPPLEMENTARY SHEET AT THE END OF | THIS DOCUMENT-'=. G. Water Supply - Pre-construction well testing
  8. The applicant shall include all test results obtained pursuant to this section in the water feasibility study. H. Water Supply — Post-construction monitoring and reporting